Oldham MX32
The MX32 from Oldham measurement and alarm unit is suitable for the protection of equipment and personnel in atmospheres which may contain flammable and toxic gases.
Oldham MX32 Control Panel Technical Specification
Type:
Wall mounted controller
Function:
Multichannel monitor
Capacity:
1 or 2 channels
Measurement:
Continuous
Display:
Liquid crystal, fixed or scrolling
Alarms:
2 independent alarm thresholds per channel
Individual programming, increasing or decreasing levels
Manual or automatic acknowledgement
Visual Alarm:
2 red LED + gas alarms per channel
1 yellow LED fault per channel
Audible Alarm:
Buzzer
Relays:
2 gas alarm relays per channel
One common relay for faults
Type of contact: NO or NC, programmable by jumpers
Power Supply:
115 V or 230 V AC
24 V DC
Power Consumption:
30 W
Breaking Capacity:
2 A /230 V AC / 30 V DC
Weather Protection:
IP 66
Bridge Type:
1 detector: maximum distance 300 m (3 x 1.5 mm2)
2 detectors: utilization of a junction box (Please consult us)
Detector with Transmitter:
One to five 2-wire detectors, 4-20 mA
One 3-wire detector, 4-20 mA
Cable 3 x 1.5 mm2 (32 Ω max. in loop mode)
Fire Detectors:
Cable 2 x 0.65 mm2
One 3-wire detector
Cable 3 x 1.5 mm2 (4.8 Ω max. in loop mode)
Weight:
1,750 g
Acknowledgement:
Manual or automatic
Operating Temperature:
-20°C to +55°C (-4°F to 131°F)
Relative Humidity:
5% to 95% RH
Approvals:
Complies with EMC and low-voltage directives